Electricity is required for various types of loads such as Domestic load, Commercial load, Industrial load, Municipal load, Irrigation load, and Traction load.
Domestic load: Electrical devices which consume power in a home. Example Ceiling fan, Television, etc.
Commercial load: Electrical devices which consume power in shopping malls, Theatres. (Lighting, Air conditioner, etc.
Industrial Load: Electrical devices which consume power in industries (Electrical motor, induction motor, etc)
Irrigation load;
To power-up, these loads, electricity needs to travel from generating station to the distribution station, and the infrastructure capable to collect and taps electricity for these loads is called an electrical grid.
During the transmission of electricity, the power network and high voltage equipment face many issues and these issues are classified into different types of faults.
Electrical fault
The abnormal flow of electric current in a power network is considered as the electrical fault or flow of electric current in an undesired path.
Power disturbance or failure in the power network lead to temporary or permanent damage to electrical equipment and power outage to the loads.
Effects of an electrical fault
An electrical fault can result in two types of damages to the electrical equipment
Thermal damage
Thermal is a word related to heat. From the name, we can easily understand that electrical fault produces heat with high temperature to the electrical equipment.
All insulation classes of the electrical equipment will have a certain limit of thermal withstand capability. Whenever the fault current or voltage exceeds the rated or operating limit then this causes to increase in thermal.
Whenever the heat or temperature exceeds the thermal withstand capability insulation, then it is considered as Thermal damage.
Thermal damage occurs very slowly because it is related to temperature. So it did not require instantaneous tripping.
Electrodynamic damage
In this case, the magnitude of the current is very high roughly 10 times or 20 times the rated or operating current. This current produces a high amount of repulsive force which can reshape or destruct the whole electrical equipment structurally.
The 10-20 times fault current can damage the electrical equipment very fastly. So it requires an instantaneous trip (without depending on time).
Instantaneous trip* Whenever the fault current or voltage exceeds the rated current circuit breaker immediately stops the flow of power within a microsecond.
Reason for an electrical fault
The electrical fault can occur for numerous reasons, some of them are addressed here,
- Insulation failure in the transmission line or electrical equipment
- Flashover of the transmission line or insulators
- The swinging of two conductors or short-circuit
- Lightning surge and switching surges increases the voltage abnormally on electrical equipment lead to electric fault
- Temporary or Permanent damage to towers and conductors lead to electric fault
- Wrong operation or wrong co-ordination in interlock
- The irresponsibility of handling electrical equipment.
- Poor maintenance of power system.
Probability of occurrence of a fault on different elements
- In overhead transmission lines conductor, the percentage of occurrence of an electrical fault is 50% due to weather condition or in other condition.
- In underground cables, the percentage of occurrence of an electrical fault is 10% because they laid below the ground. So the chances of affection due to weather condition is less.
- In switchgear including CTs and PT's the percentage of occurrence of an electrical fault is 10% to 15%.
- In power transformers, the percentage of occurrence of an electrical fault is 15%.
Different types of fault in overhead transmission line
- Series fault (open condition fault)
- Shunt fault (close condition fault)
Series fault
Example of series fault
- Explode fuses cause an open circuit
- The unbalance opening of the circuit breaker (A circuit breaker which cannot capable to open all three phases is considered as the open circuit)
Characterization of series fault
- Voltage and frequency increase with a decrease in magnitude current
Shunt fault
Example of shunt fault
- The line to line fault
- Triple phase fault (line to line to line fault)
- The line to ground fault
- Double line to ground fault
Characteristics of shunt fault
- Current increases with a decrease in voltage and frequency
Categorization of fault (symmetrical and asymmetrical fault)
- Symmetrical fault
- unsymmetrical fault
Symmetrical fault
- Line-Line-Line fault ( All the transmission line touch each other or becomes short circuit)
- Line-Line-Line-Ground fault (All the transmission line touches the ground)
For example:
Asymmetrical fault
- Line-Line fault (Two phases [R and Y] of the 3 phase transmission line touches each other)
- Line-Ground fault (Single phase [ R] of the 3 phase transmission line broken and touches the ground)
- Line-Line-Ground fault (Two phases[ R and Y] of the 3 phase transmission line touches the ground)
If you’ve been waiting a long time for XNXUBD 2021 Nvidia News, we have good news for you. Nvidia Corporation, the largest U.S. based multinational processing unit-based GPU manufacturing company, has shared a step-by-step guide on Xnxubd 2021 Nvidia New Video Download. Since Nvidia GeForce has always been the preferred choice for Graphic Cards, XNXUBD 2021 update is said to bring some significant changes to its performance, such as reduced latency rate, smoothness and animation, etc.
ReplyDeletexnxubd-2021-nvidia-news